Topics
Subnavigation
Topics
Electromagnetic fields
- What are electromagnetic fields?
- High-frequency fields
- Radiation protection in mobile communication
- Static and low-frequency fields
- Radiation protection relating to the expansion of the national grid
- Radiation protection in electromobility
- The Competence Centre for Electromagnetic Fields
Optical radiation
- What is optical radiation?
- UV radiation
- Visible light
- Infrared radiation
- Application in medicine and wellness
- Application in daily life and technology
Ionising radiation
- What is ionising radiation?
- Radioactivity in the environment
- Applications in medicine
- Applications in daily life and in technology
- Radioactive radiation sources in Germany
- Register high-level radioactive radiation sources
- Type approval procedure
- Items claiming to provide beneficial effects of radiation
- Cabin luggage security checks
- Radioactive materials in watches
- Ionisation smoke detectors (ISM)
- Radiation effects
- What are the effects of radiation?
- Effects of selected radioactive materials
- Consequences of a radiation accident
- Cancer and leukaemia
- Hereditary radiation damage
- Individual radiosensitivity
- Epidemiology of radiation-induced diseases
- Ionising radiation: positive effects?
- Radiation protection
- Nuclear accident management
- Service offers
-
The BfS
Subnavigation
The BfS
- Working at the BfS
- About us
- Science and research
- Laws and regulations
- Radiation Protection Act
- Ordinance on Protection against the Harmful Effects of Ionising Radiation
- Ordinance on Protection against the Harmful Effects of Non-ionising Radiation in Human Applications (NiSV)
- Frequently applied legal provisions
- Dose coefficients to calculate radiation exposure
- Links
Limit values for static and low frequency fields
- The 26th Ordinance Implementing the Federal Immission Control Act (Ordinance on electromagnetic fields – Verordnung über elektromagnetische Felder zum Bundes-Immissionsschutzgesetz – 26 BImSchV) sets limits to protect the public against health hazards due to electric and magnetic fields from direct current and low frequency systems.
- Low frequency installations shall not exceed the limits in places intended for non-temporary presence of humans when operated at maximum capacity. The same is required for direct current installations in places intended for long-term, or temporary presence of humans.
- According to the present state of knowledge, compliance with these limits will ensure health protection of the public even under permanent exposure.
The 26th Ordinance Implementing the Federal Immission Control Act (Ordinance on electromagnetic fields – Verordnung über elektromagnetische Felder zum Bundes-Immissionsschutzgesetz – 26 BImSchV) sets limits to protect the public against health hazards due to electric and magnetic fields from direct current and low frequency systems.
The Twenty-sixth Ordinance Implementing the Federal Immission Control Act
The Ordinance has been in force since 1997 and was amended in August 2013. It is based on recommendations of the German Commission on Radiological Protection (Deutsche Strahlenschutzkommission, SSK) and the International Commission on Non-Ionizing Radiation Protection (ICNIRP).
The recommendations of the above commissions rest on scientific evidence of health relevant biological effects that may be produced by electric and magnetic fields.
The 26th BImSchV applies to all stationary low frequency and direct current installations
The 26th BImSchV applies to all stationary low frequency and direct current installations for electric power transformation and distribution operated at voltages exceeding 1000 (for stationary low frequency) or 2000 (for direct current installations) Volts. This includes high-voltage lines, traction current lines, electrical substations, transformer stations and power conversion systems (for high-voltage direct-current transmission, HVDC transmission).
The 26th BImSchV does not apply to domestic electric appliances and power lines. However, the limit values set by the Ordinance may be used to evaluate the risk with regard to potential effects of static and low frequency fields from domestic electric appliances and power lines.
Low frequency installations shall not exceed the limits in places intended for non-temporary presence of humans when operated at maximum capacity. The same is required for direct current installations in places intended for long-term, or temporary presence of humans.
Since its amendment, the 26th BlmSchV contains limits covering both the whole low frequency range (1 Hertz to 9 Kilohertz) and static magnetic fields for the first time. The previous ordinance only covered fields from the traction power lines and overhead lines as well as fields from the 50-Hz-power supply grid.
Frequency f (Hertz) | Electric field strength E (kilovolt per metre) | Magnetic flux density B (microtesla) |
---|---|---|
0 | - | 5001) |
1 - 8 | 5 | 40.000/f2) |
8 - 25 | 52) | 5.000/f |
25 - 50 | 5 | 2003) |
50 - 400 | 250/f | 200 |
400 - 3.000 | 250/f | 80.000/f |
3.000 - 10.000.000 | 0,083 | 27 |
|
Limit values help safeguard public health
According to the present state of knowledge, compliance with these limits will ensure health protection of the public even under permanent exposure.
State of 2023.01.30